Hybrid Model for Analysis of Ground Fault Current Distribution


Vujević, Slavko; Balaž, Zdenko; Modrić, Tonći; Sarajčev, Petar
Hybrid Model for Analysis of Ground Fault Current Distribution // International review of civil engineering, 7 (2012), 2; 4035-4045 (međunarodna recenzija, članak, znanstveni)


CROSBI ID: 587644 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Hybrid Model for Analysis of Ground Fault Current Distribution

Autori
Vujević, Slavko ; Balaž, Zdenko ; Modrić, Tonći ; Sarajčev, Petar

Izvornik
International review of civil engineering (2036-9913) 7 (2012), 2; 4035-4045

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni

Ključne riječi
Hybrid Model; Electromagnetic Model; Transmission Line Model; Finite Element Technique; Phase-to-Ground Fault Current Distribution; Buried Non-Insulated Conductive Parts of Grounding System; Conductive Coupling; Inductive Coupling

Sažetak
This paper presents a hybrid numerical model for computation of the phase-to-ground fault current distribution between soil and neutral conductors of grounding system. Hybrid model is combination of electromagnetic model and transmission line model. In numerical realization, the finite element technique is used. Using electromagnetic model, conductive coupling between all buried non-insulated conductive parts of grounding system is taken into account. Using transmission line model, inductive coupling between phase conductors and ground wires of parallel overhead power lines is used. Similar transmission line approach is used for parallel power cable lines and cable line grounding wires. In computer programs developed for ground fault current distribution, the conductive coupling between all buried non-insulated conductive parts of grounding system can be taken into account or neglected. From the numerous numerical examples, it can be deduced that one can introduce a significant error by neglecting the conductive coupling. In presented numerical example, error caused by neglecting the conductive coupling between all buried non-insulated conductive parts of grounding system can be observed in rms values and phase angles of currents and potentials.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika

Napomena
Rad spada u kategoriju A jer je objavljen u znanstvenom časopisu koji je zastupljen u SCI– Expanded bazi, odnosno WoS-u ; (NN 84/05.)



POVEZANOST RADA


Projekti:
023-0000000-3271 - Razvoj naprednih algoritama za modeliranje elektromagnetskih pojava (Vujević, Slavko, MZOS ) ( CroRIS)

Ustanove:
Fakultet elektrotehnike, strojarstva i brodogradnje, Split

Profili:

Avatar Url Zdenko Balaž (autor)

Avatar Url Petar Sarajčev (autor)

Avatar Url Slavko Vujević (autor)

Avatar Url Tonći Modrić (autor)

Citiraj ovu publikaciju:

Vujević, Slavko; Balaž, Zdenko; Modrić, Tonći; Sarajčev, Petar
Hybrid Model for Analysis of Ground Fault Current Distribution // International review of civil engineering, 7 (2012), 2; 4035-4045 (međunarodna recenzija, članak, znanstveni)
Vujević, S., Balaž, Z., Modrić, T. & Sarajčev, P. (2012) Hybrid Model for Analysis of Ground Fault Current Distribution. International review of civil engineering, 7 (2), 4035-4045.
@article{article, author = {Vujevi\'{c}, Slavko and Bala\v{z}, Zdenko and Modri\'{c}, Ton\'{c}i and Saraj\v{c}ev, Petar}, year = {2012}, pages = {4035-4045}, keywords = {Hybrid Model, Electromagnetic Model, Transmission Line Model, Finite Element Technique, Phase-to-Ground Fault Current Distribution, Buried Non-Insulated Conductive Parts of Grounding System, Conductive Coupling, Inductive Coupling}, journal = {International review of civil engineering}, volume = {7}, number = {2}, issn = {2036-9913}, title = {Hybrid Model for Analysis of Ground Fault Current Distribution}, keyword = {Hybrid Model, Electromagnetic Model, Transmission Line Model, Finite Element Technique, Phase-to-Ground Fault Current Distribution, Buried Non-Insulated Conductive Parts of Grounding System, Conductive Coupling, Inductive Coupling} }
@article{article, author = {Vujevi\'{c}, Slavko and Bala\v{z}, Zdenko and Modri\'{c}, Ton\'{c}i and Saraj\v{c}ev, Petar}, year = {2012}, pages = {4035-4045}, keywords = {Hybrid Model, Electromagnetic Model, Transmission Line Model, Finite Element Technique, Phase-to-Ground Fault Current Distribution, Buried Non-Insulated Conductive Parts of Grounding System, Conductive Coupling, Inductive Coupling}, journal = {International review of civil engineering}, volume = {7}, number = {2}, issn = {2036-9913}, title = {Hybrid Model for Analysis of Ground Fault Current Distribution}, keyword = {Hybrid Model, Electromagnetic Model, Transmission Line Model, Finite Element Technique, Phase-to-Ground Fault Current Distribution, Buried Non-Insulated Conductive Parts of Grounding System, Conductive Coupling, Inductive Coupling} }

Časopis indeksira:


  • Web of Science Core Collection (WoSCC)
    • Science Citation Index Expanded (SCI-EXP)
    • SCI-EXP, SSCI i/ili A&HCI
  • Scopus


Uključenost u ostale bibliografske baze podataka::


  • Science Citation Index Expanded™ ( SciSearch) - ISI Thomson
  • Journal Citation Reports/Science Edition - ISI Thomson
  • Elsevier Bibliographic Database SCOPUS
  • Academic Search Complete - EBSCO Information Services
  • Cambridge Scientific Abstracts - CSA/CIG





Contrast
Increase Font
Decrease Font
Dyslexic Font