Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 316825

Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software


Nikolovski, Srete; Marić, Predrag; Baus, Zoran
Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software // Journal of electrical engineering, 58 (2007), 4; 207-213 (međunarodna recenzija, članak, znanstveni)


CROSBI ID: 316825 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software

Autori
Nikolovski, Srete ; Marić, Predrag ; Baus, Zoran

Izvornik
Journal of electrical engineering (1335-3632) 58 (2007), 4; 207-213

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni

Ključne riječi
electric field ; magnetic field ; transformer station ; electromagnetic compatibility ; moment method ; computer program

Sažetak
This paper presents calculations of the electric and magnetic fields of complex busbars, transformers and transmission line structures at the transmission power station 400/110 kV Ernestinovo. By constructing and bringing the TS 400/110 kV Ernestinovo in operation, it was expected that electric and magnetic fields would arise within and outside the fence of the transformer station. The fundamental sources of low frequency electromagnetic fields in the TS Ernestinovo are the primary elements of the 400 and 110 kV open substations as well as the connected 400 kV and 110 kV overhead lines. Due to the complexity of the geometry of the substation elements, it was necessary to apply a three- dimensional approach to the calculation and analysis of the electromagnetic field. Calculations of electromagnetic fields were conducted for quasi-static states of electrical values at a power frequency of 50 Hz. The calculated electric and magnetic fields were compared with permissible levels according to Croatian regulations. The maximum permissible levels for the electric field and magnetic flux density were found to be exceeded at some locations in the station.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
165-1651481-1482 - Kvaliteta i pouzdanost pogona EES Hrvatske na regionalnom tržištu el. energije (Nikolovski, Srete, MZOS ) ( CroRIS)

Ustanove:
Fakultet elektrotehnike, računarstva i informacijskih tehnologija Osijek

Profili:

Avatar Url Srete Nikolovski (autor)

Avatar Url Zoran Baus (autor)

Avatar Url Predrag Marić (autor)

Citiraj ovu publikaciju:

Nikolovski, Srete; Marić, Predrag; Baus, Zoran
Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software // Journal of electrical engineering, 58 (2007), 4; 207-213 (međunarodna recenzija, članak, znanstveni)
Nikolovski, S., Marić, P. & Baus, Z. (2007) Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software. Journal of electrical engineering, 58 (4), 207-213.
@article{article, author = {Nikolovski, Srete and Mari\'{c}, Predrag and Baus, Zoran}, year = {2007}, pages = {207-213}, keywords = {electric field, magnetic field, transformer station, electromagnetic compatibility, moment method, computer program}, journal = {Journal of electrical engineering}, volume = {58}, number = {4}, issn = {1335-3632}, title = {Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software}, keyword = {electric field, magnetic field, transformer station, electromagnetic compatibility, moment method, computer program} }
@article{article, author = {Nikolovski, Srete and Mari\'{c}, Predrag and Baus, Zoran}, year = {2007}, pages = {207-213}, keywords = {electric field, magnetic field, transformer station, electromagnetic compatibility, moment method, computer program}, journal = {Journal of electrical engineering}, volume = {58}, number = {4}, issn = {1335-3632}, title = {Electromagnetic Field Calculation of Transformer Station 400/110 kV Ernestinovo Using CDEGS Software}, keyword = {electric field, magnetic field, transformer station, electromagnetic compatibility, moment method, computer program} }

Časopis indeksira:


  • Web of Science Core Collection (WoSCC)
    • Science Citation Index Expanded (SCI-EXP)
    • SCI-EXP, SSCI i/ili A&HCI
  • Scopus


Uključenost u ostale bibliografske baze podataka::


  • INSPEC





Contrast
Increase Font
Decrease Font
Dyslexic Font