Loss of Excitation Protection Testing by Transient Playback of EMTP Simulation Results
Loss of Excitation Protection Testing by Transient Playback of EMTP Simulation Results // Proceedings of the 14th International Conference on Power System Protection / Babnik, Tadeja ; Gubina, Ferdinand (ur.).
Ljubljana: Fakulteta za elektrotehniko (Ljubljana), 2004. str. 255-260 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), stručni)
CROSBI ID: 287269 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Loss of Excitation Protection Testing by Transient Playback of EMTP Simulation Results
Autori
Nemec, Darko ; Bulat, Hrvoje ; Stojsavljević, Milan ; Klapčić, Čelio
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), stručni
Izvornik
Proceedings of the 14th International Conference on Power System Protection
/ Babnik, Tadeja ; Gubina, Ferdinand - Ljubljana : Fakulteta za elektrotehniko (Ljubljana), 2004, 255-260
Skup
14th International Conference On Power System Protection
Mjesto i datum
Bled, Slovenija, 28.09.2004. - 01.10.2004
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
EMTP simulation; field test; generator protection; loss of excitation
Sažetak
Loss-of-excitation protection of a large synchronous generator was tested at the site by injecting simulated generator current and voltage signals obtained from the EMTP simulation for various fault scenarios. The protection operates on directional current principle with overcurrent / undervoltage control. In order to achieve proper coordination of the protection with the unit's underexcitation limiter a new setting of the protection was proposed. By recording the protection response during tests its correct operation has been proved. Finally, the validity of the new setting has been assessed by checking the protection operating characteristic during primary field tests.