Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms


Ivankovic, I; Rubesa, R; Rekic, M; Skok, S
Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms // Conference: 2020 IEEE/PES Transmission and Distribution Conference and Exposition (T&D)
Chicago (IL), Sjedinjene Američke Države, 2020. str. 264-123 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 1184612 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms

Autori
Ivankovic, I ; Rubesa, R ; Rekic, M ; Skok, S

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Skup
Conference: 2020 IEEE/PES Transmission and Distribution Conference and Exposition (T&D)

Mjesto i datum
Chicago (IL), Sjedinjene Američke Države, 12.10.2020. - 15.10.2020

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
Synchrophasors, broken conductor, imbalance, symetrical components

Sažetak
Three phase power system in some circumstances suffers from imbalances in the operation. This condition might lead to more serious contingencies, operational security risks and can leads to higher losses and insulation degradation. One phase breakage, high resistance fault or two phase operation in the power system (short circuit or earth fault) is a case of longitudinal, serial failure. Such condition causes imbalance in the three phase system and appearance of inverse and zero sequence components. In the control room this condition can be detected by alarms from the relay protection devices (in case the function is activated) or in the higher bias and measurement error detected by the state estimation algorithm. In this paper, a detection algorithm based on synchrophasor data is presented. The algorithm in a centralized application in the control center is based on the symmetrical components calculated in the PMU and collected in the Phasor Data Concentrator (PDC).

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Ustanove:
Sveučilište Sjever, Koprivnica

Profili:

Avatar Url Srđan Skok (autor)

Avatar Url Igor Ivanković (autor)

Avatar Url Rajko Rubeša (autor)


Citiraj ovu publikaciju:

Ivankovic, I; Rubesa, R; Rekic, M; Skok, S
Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms // Conference: 2020 IEEE/PES Transmission and Distribution Conference and Exposition (T&D)
Chicago (IL), Sjedinjene Američke Države, 2020. str. 264-123 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Ivankovic, I., Rubesa, R., Rekic, M. & Skok, S. (2020) Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms. U: Conference: 2020 IEEE/PES Transmission and Distribution Conference and Exposition (T&D).
@article{article, author = {Ivankovic, I and Rubesa, R and Rekic, M and Skok, S}, year = {2020}, pages = {264-123}, keywords = {Synchrophasors, broken conductor, imbalance, symetrical components}, title = {Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms}, keyword = {Synchrophasors, broken conductor, imbalance, symetrical components}, publisherplace = {Chicago (IL), Sjedinjene Ameri\v{c}ke Dr\v{z}ave} }
@article{article, author = {Ivankovic, I and Rubesa, R and Rekic, M and Skok, S}, year = {2020}, pages = {264-123}, keywords = {Synchrophasors, broken conductor, imbalance, symetrical components}, title = {Rare Transmission Anomaly and Fault Detection based on Synchrophasors in Control Rooms}, keyword = {Synchrophasors, broken conductor, imbalance, symetrical components}, publisherplace = {Chicago (IL), Sjedinjene Ameri\v{c}ke Dr\v{z}ave} }




Contrast
Increase Font
Decrease Font
Dyslexic Font