Pregled bibliografske jedinice broj: 1157806
Measurement of large power transformer winding temperature by inducative voltage correction method
Measurement of large power transformer winding temperature by inducative voltage correction method // ETZ-Archiv, 11 (1989), 2; 63-70 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 1157806 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Measurement of large power transformer winding
temperature by inducative voltage correction method
Autori
Godec, Zdenko
Izvornik
ETZ-Archiv (0170-1703) 11
(1989), 2;
63-70
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
power transformers, measurements, winding resistance, winding temperature rise, inductive voltage correction method, transient effects, errors reduction
Sažetak
An universal and inexpensive inductive voltage correction method for winding resistance measurement has been analyzed. This method enables winding temeperature rise determination by change of its resistance even in the larges transformers, despite of long-lasting transient phenomenon of DC measuring current. Errors have been analyzed in detail. Due to the increased temperature rise determination error, the correction method should be used only when the transient effects cannot be reduced by the increase of DC measuring source voltage to duration shorter than 2 min.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
Citiraj ovu publikaciju:
Časopis indeksira:
- Scopus