Exergy analysis of an air conditioning process
The exergy analysis of an air conditioning process in wintertime is presented in this paper. This process consists of mixing outdoor air with conditioned air, heating, humidifying, and reheating the air mixture. The air is heated in the heat exchangers by warm water at a temperature of 80/60 °C and humidified by spraying water at a temperature of 12 °C. The ratio of the mass flow rates of outdoor and conditioned air is varied, and it is upon this variable that the exergy analysis is performed. It is shown that the heat transfer rate in the heat exchangers is the smallest at the ratio of mass flow rates of outdoor and conditioned air g1 = 0, 45. The greatest exergy destruction is apparent on the air heaters, and the maximum exergy efficiency of the whole process is 0, 71 is achieved at the ratio g1 = 0, 45. According to the exergy criterion, this air conditioning is a relatively efficient process.
Air conditioning ; exergy destruction ; exergy efficiency