Interlocking schema based on GOOSE messages tested with IEC61850 protocol simulator (CROSBI ID 673352)
Prilog sa skupa u zborniku | ostalo | međunarodna recenzija
Podaci o odgovornosti
Pregrad, Goran ; Višić, Ivan
engleski
Interlocking schema based on GOOSE messages tested with IEC61850 protocol simulator
Numerical relays joined with IEC61850 standard opened a great possibility to migrate interlocking logic in substations from hardwired to logic executed by numerical control relays. This introduced a big savings in time and materials required for hardwire solutions but it also created a need to develop new testing procedures and tools that will allow testing it and fully exploiting its advantages. Further more such a products are needed for all other functionalities which are migrated from wiring to IEC61850 communication based solutions. The study case for this article is refurbishment of the 400/220/110kV Mintia substation. A rather big SS of roughly forty bays needs to be refurbished bay per bay, while rest of it is in operation. With such a setting it was a challenge to prove functionality of interlocking system with only typical bays prepared for factory acceptance test. It was decided to use IEC61850 protocol simulator in order to make interlocking functional and available for testing and presenting to customer. As the configuration of substation is rather complicated, including transfer busbar and more sections on regular busbars, required logic was complicated. In order to test complete logic or interlocking schema it was necessary to simulate change of state for large number of elements.
IEC61850, interlocking, GOOSE
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1-8.
2011.
objavljeno
Podaci o matičnoj publikaciji
Proceedings Papers PAC World 2011.
Apostolov, Alex
Dublin: PAC world magazine
Podaci o skupu
PAC world conference 2011.
predavanje
27.06.2011-30.06.2011
Dublin, Irska