Heat pump system efficiency comparison of different renewable energy sources – A family house case study in Zagreb city area (CROSBI ID 259670)

Prilog u časopisu | prethodno priopćenje | međunarodna recenzija

Macenić, Marija ; Kurevija, Tomislav ; Kapuralić, Josipa Heat pump system efficiency comparison of different renewable energy sources – A family house case study in Zagreb city area // Rudarsko-geološko-naftni zbornik, 33 (2018), 5; 13-25. doi: 10.17794/rgn.2018.5.2

Podaci o odgovornosti

Macenić, Marija ; Kurevija, Tomislav ; Kapuralić, Josipa

engleski

Heat pump system efficiency comparison of different renewable energy sources – A family house case study in Zagreb city area

The wider Zagreb city area, the capital city of the Republic of Croatia, has signifi cant potential for major implementation of geothermal heat pump systems in not just the residential sector, but in the commercial sector as well. Geothermal heat pumps often cumulatively describe diff erent earth energy heat exchanger installations, from groundwater up to shallow ground horizontal and borehole heat exchanger installations. The Zagreb area is especially favourable for both hydrogeological and thermogeological parameters, which allows for the implementation of diff erent designs for residential and commercial heating and cooling. An analysis of comparative energy and economic advantages of heating and cooling with heat pump systems (air, ground or groundwater) was made for the capital city of Zagreb. Since heat pump systems in residential areas are always a higher- class investment, there is often a need for year- round heating since projects increasingly incorporate outdoor swimming pools. Up till now, many authors investigated a comparison of winter heating energy costs for diff erent heat pump systems. However, outdoor swimming pools sometimes consume as much heating energy during the spring- summer-autumn seasons, as do houses in the autumn- winter-spring seasons. Since air temperatures during the spring-summer seasons are much more favourable than sub-cooled ground or groundwater temperatures, air-source heat pumps when used during the whole year for heating, could off set an economically unfavourable coeffi cient of performance (COP) during the coldest days of winter. On a real residential home, currently in the construction phase, techno-economic analysis was performed comparing the seasonal performance factor (SPF) for different heat pump systems during year-round heating.

shallow geothermal energy, heat pump, thermogeology, borehole heat exchanger, groundwater

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

33 (5)

2018.

13-25

objavljeno

0353-4529

10.17794/rgn.2018.5.2

Povezanost rada

Rudarstvo, nafta i geološko inženjerstvo

Poveznice
Indeksiranost