Control variable selection for the corrective control of voltages and reactive power flows (CROSBI ID 670594)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Tomašević, Frano ; Pavić, Ivica ; Delimar, Marko Control variable selection for the corrective control of voltages and reactive power flows // Proceedings of 2016 51st International Universities Power Engineering Conference (UPEC). Coimbra: Institute of Electrical and Electronics Engineers (IEEE), 2016. str. 1-6 doi: 10.1109/UPEC.2016.8114144

Podaci o odgovornosti

Tomašević, Frano ; Pavić, Ivica ; Delimar, Marko

engleski

Control variable selection for the corrective control of voltages and reactive power flows

A sequential search strategy for the control variable subset selection, used for optimal power system voltage control and reactive power management, is presented in this paper. The objective of the presented selection method is to eliminate the redundant control variables which have small impact on the reactive power optimization (RPO) objective function and/or constraints. Selected control variable set is used for correcting the power system state in which the operational limits are violated. The candidate control variables are evaluated based not just on their impact on the out-of-bound variables, but also on the overall power system state. Sensitivity analysis, based on power flow calculation, was conducted for each candidate control variable and the results were used as an input data for the sequential search method. Considering the RPO is inherently a mixed integer nonlinear programming (MINLP) problem, the genetic algorithm (GA) was used for solving the optimization problem. The efficiency of the presented method was tested on IEEE test systems. Simulation results are presented for IEEE 118-bus test system.

Voltage control ; Reactive power ; Optimization ; Power system stability

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

1-6.

2016.

objavljeno

10.1109/UPEC.2016.8114144

Podaci o matičnoj publikaciji

Proceedings of 2016 51st International Universities Power Engineering Conference (UPEC)

Coimbra: Institute of Electrical and Electronics Engineers (IEEE)

978-1-5090-4650-8

Podaci o skupu

2016 51st International Universities Power Engineering Conference (UPEC)

predavanje

06.09.2016-09.09.2016

Coimbra, Portugal

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost