Partial Discharge Diagnosis of Medium Voltage Power Cables (CROSBI ID 670456)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Garma, Tonko ; Mučić, Dragan ; Petrović, Goran ; Kilić, Tomislav
engleski
Partial Discharge Diagnosis of Medium Voltage Power Cables
In this paper, the basic principles of partial discharges (PD) are described, including off- line and on-line methods and the basic concepts for understanding and using aforementioned approaches are clarified. Considering the large number of cables in the distribution network, it is unrealistic to expect all cables to be analyzed in detail. For this purpose it is useful to use a hand-held PD detector to make online pre-selection of cables for a more detailed off-line diagnostic analysis. Selected sections of the distribution grid are disconnected and analyzed in detail using off- line method. PD in the cable can be located by analyzing the measured data. Other diagnostic methods provide general insight into the state of insulation while PD enables localization of the malfunction section. In this way a badly made junction or cable termination can be located and preventively replaced.
Partial discharges (PD), on-line and off-line method, cable insulation.
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1-5.
2018.
objavljeno
Podaci o matičnoj publikaciji
Smagrimet 2018
Podaci o skupu
First International Colloquium on Smart Grid Metrology (SmaGriMet 2018)
predavanje
24.04.2018-27.04.2018
Split, Hrvatska