Direct time domain analytical solution for the transient impedance of the horizontal grounding electrode (CROSBI ID 662833)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Šesnić, Silvestar ; Poljak, Dragan
engleski
Direct time domain analytical solution for the transient impedance of the horizontal grounding electrode
The paper deals with a derivation of simple and efficient analytical solution for the calculation of transient impedance of the horizontal grounding electrode. The Generalized Telegrapher’s Equation for spatial distribution of the scattered voltage in the frequency domain is used to derive the transient voltage at the feed point of the grounding electrode. Solution is obtained by using the Inverse Laplace Transform and Cauchy residue theorem. Transient impedance is determined as a ratio of time domain voltage and (lightning) current at the feeding point. Some illustrative numerical results are given.
Analytical modelling ; transient impedance ; grounding electrode
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
E01-07
2018.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the 2nd URSI Atlantic Radio Science Meeting
Podaci o skupu
2nd URSI Atlantic Radio Science Meeting (AT-RASC 2018)
predavanje
28.05.2018-01.06.2018
Las Palmas de Gran Canaria, Španjolska