Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Carbon monoxide and carbon dioxide in closed-type power transformers (CROSBI ID 244342)

Prilog u časopisu | stručni rad | međunarodna recenzija

Hadži-Skerlev, Anđela ; Vrsaljko, Dijana ; Haramija, Veronika ; Musulin, Božena Carbon monoxide and carbon dioxide in closed-type power transformers // Energija : časopis Hrvatske elektroprivrede, 61 (2012), Special Issue; 28-34

Podaci o odgovornosti

Hadži-Skerlev, Anđela ; Vrsaljko, Dijana ; Haramija, Veronika ; Musulin, Božena

engleski

Carbon monoxide and carbon dioxide in closed-type power transformers

Gases carbon monoxide (CO) and carbon dioxide (CO2) are formed in transformers in larger quantities as a product of degradation of cellulose, than by oxidation of oil. In transformers with closed-type breathing system, without any indication of failure or fault, it was observed that the concentrations of CO are higher than the typical values according to IEC 60599 and CO2/CO ratios lower than 3 frequently have been found. This paper presents results of laboratory investigation of some influence parameters on formation gases CO and CO2. The typical values for CO as well scheme concerning their ratios need to be revised in standard IEC 60599. The criteria need to be established separately for closed type transformers.

carbon monoxide ; carbon dioxide ; cellulose ; mineral oil

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

61 (Special Issue)

2012.

28-34

objavljeno

0013-7448

1849-5346

Povezanost rada

Elektrotehnika