A New Method for Estimation of Time Parameters of Standard and Non-Standard Switching Impulse Voltages (CROSBI ID 241811)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Filipović-Grčić, Božidar ; Filipović-Grčić, Dalibor A New Method for Estimation of Time Parameters of Standard and Non-Standard Switching Impulse Voltages // International journal of electrical power & energy systems, 96 (2017), 126-131. doi: 10.1016/j.ijepes.2017.10.001

Podaci o odgovornosti

Filipović-Grčić, Božidar ; Filipović-Grčić, Dalibor

engleski

A New Method for Estimation of Time Parameters of Standard and Non-Standard Switching Impulse Voltages

In this paper a new method for estimation of time parameters of standard and non-standard switching impulse voltages is presented. Method is based on estimation of time difference between true and virtual origin of the switching impulse waveform. An analytical expression was derived for calculation of time to peak, which is more accurate than the expression given in IEC 60060-1. The presented method was verified with mathematically generated double-exponential waveforms and waveforms given in IEC 61083-2 with time to peak values within the range 20-300 µs and time to half values within the range 1000-4000 µs. An experimental verification of the proposed method was successfully demonstrated by comparison with an approved impulse voltage measuring system.

Switching impulse voltages ; time and amplitude parameters ; IEC 60060-1 ; high-voltage test techniques

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

96

2017.

126-131

objavljeno

0142-0615

1879-3517

10.1016/j.ijepes.2017.10.001