Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

New Method for Prediction of Insulating Liquid AC Breakdown (CROSBI ID 236908)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Marković, Mladen ; Štih, Željko New Method for Prediction of Insulating Liquid AC Breakdown // IEEE transactions on dielectrics and electrical insulation, 24 (2017), 1; 437-454. doi: 10.1109/TDEI.2016.005940

Podaci o odgovornosti

Marković, Mladen ; Štih, Željko

engleski

New Method for Prediction of Insulating Liquid AC Breakdown

Paper compares three most widely used methods in insulating liquid breakdown prediction: cumulative stress method, stressed electrode area and stressed liquid volume. Breakdowns were measured on Midel 7131 on OTS100AF oil tester with two different electrodes at three gap distances. Prediction capabilities of three methods were tested with respect to results of conducted measurements and research done by other authors. The utilization of these methods is enhanced by application of numerical calculation of electric field. It is shown how these methods are interrelated and a proposal for their unification is given. Unification model is confirmed on measurements conducted in this and other research papers.

ac breakdown, stressed liquid volume, stressed electrode area, cumulative stress, numerical calculation, streamline sweep area, Midel 7131, liquid nitrogen, mineral oil

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

24 (1)

2017.

437-454

objavljeno

1070-9878

10.1109/TDEI.2016.005940

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost