Power transformer main insulation design improvement using BEM and FEM (CROSBI ID 633470)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Marković, Mladen ; Štih, Željko ; Ćućić, Branimir Power transformer main insulation design improvement using BEM and FEM // EUROCON, 2013 IEEE. 2013

Podaci o odgovornosti

Marković, Mladen ; Štih, Željko ; Ćućić, Branimir

engleski

Power transformer main insulation design improvement using BEM and FEM

Insulation system is one of the most important parts of power transformer. Theoretical background for insulation design is given, which includes explanation of dielectric properties of main insulation materials, their withstand to breakdown voltage, their verification by dielectric tests, and statistical data based theory for breakdown probability. Two known numerical methods (BEM and FEM) for calculation of electric field are used and for each numerical method an appropriate model of transformer is made. Safety factors for main insulation between HV and LV winding are calculated after which the oil gap width is reduced. Additional analysis of safety factors and field non- uniformity along windings is performed.

numerical calculation; boundary element method; finite element method; electric field; power transformer

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

2013.

objavljeno

Podaci o matičnoj publikaciji

EUROCON, 2013 IEEE

Podaci o skupu

EUROCON, 2013 IEEE

predavanje

01.07.2013-04.07.2013

Zagreb, Hrvatska

Povezanost rada

Elektrotehnika