Napredna pretraga

Pregled bibliografske jedinice broj: 789347

Increasing flexibility of coal power plant by control system modifications


Marušić, Ante; Lončar, Dražen; Batelić, Jakov; Franković, Valdi
Increasing flexibility of coal power plant by control system modifications // Proceedings of the 10th Conference on Sustainable Development of Energy, Water and Environment Systems
Dubrovnik, Hrvatska, 2015. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


Naslov
Increasing flexibility of coal power plant by control system modifications

Autori
Marušić, Ante ; Lončar, Dražen ; Batelić, Jakov ; Franković, Valdi

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
Proceedings of the 10th Conference on Sustainable Development of Energy, Water and Environment Systems / - , 2015

Skup
10th Conference on Sustainable Development of Energy, Water and Environment Systems

Mjesto i datum
Dubrovnik, Hrvatska, 27.9.-2.10.2015.

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
Coal Powered Plants; Flexible Generation; Thermal Stress; Simulation

Sažetak
Expanding implementation of intermittent renewable energy sources has already started to change the role of thermal power plants in energy systems across Europe. Traditionally base load plants are now forced to operate as peaking plants. Familiar transition in upcoming years is expected in Croatia and coal power plant operators are preparing accordingly. To evaluate control system operation and cycling capabilities for flexible operation of selected 210 MW coal plant, series of tests with different load gradients were performed and results were thoroughly analyzed. Several unexpected readings were observed, usually caused by malfunctioning sensors and equipment resulting in unexpected oscillations of superheated steam temperature. To assess optimal steam temperature control parameters, one dimensional simulation of steam superheating was conducted and control system was tuned to satisfy temperature differences based on guidelines for flexible operation. Changes of control system structures and parameters will be recommended in order to improve superheated steam temperature behavior and to assure stable plant operation during load changes.

Izvorni jezik
Engleski

Znanstvena područja
Strojarstvo



POVEZANOST RADA


Ustanove
Fakultet strojarstva i brodogradnje, Zagreb