Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Steady-state Temperature Rises of ONAN/ONAF/OFAF Transformers (CROSBI ID 94026)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Godec, Zdenko ; Šarunac, Radovan Steady-state Temperature Rises of ONAN/ONAF/OFAF Transformers // IEE proceedings. Science, measurement and technology, 139 (1992), 5; 448-454

Podaci o odgovornosti

Godec, Zdenko ; Šarunac, Radovan

engleski

Steady-state Temperature Rises of ONAN/ONAF/OFAF Transformers

In the piping between the tank of a 40 MVA transformer, originally designed for ONAN/ONAF cooling combination, and its bank of radiators, a propeller oil pump was installed. Characteristic temperature rises were measured before and after installation of the pump. The results were applied to the development of a new algorithm for calculation of windings and oil steady-state temperature rises of ONAN/ONAF/OFAF transformers. The mathematical model is briefly described in the paper, and the basic thermal characteristics of transformers with this combination of cooling types are described. Installation of the oil pump can make transformer cooling more efficient provided that certain conditions are satisfied.

Power transformer ; cooling types ; winding temperature ; mathematical models ; temperature rise ; measurement

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

139 (5)

1992.

448-454

objavljeno

1350-2344

1359-7094

Povezanost rada

nije evidentirano