Input Shaping of the Synchronous Generator for Reduction of Self-induced Oscillations (CROSBI ID 215999)
Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Jolevski, Danijel ; Bego, Ozren
engleski
Input Shaping of the Synchronous Generator for Reduction of Self-induced Oscillations
This article suggests the application of input shaping for the elimination of electromechanical oscillations arising from changes in the operating point of the synchronous generator. Poorly damped poles are the cause of electromechanical oscillations of the synchronous generator. Various power system stabilizers (PSS) are now used to reduce the electromechanical oscillations. Input shaping is a feedforward control and therefore does not require the measurement of electrical and mechanical quantities of the synchronous generator unlike the PSS. It is possible to apply the input shaping for the excitation system of synchronous generators with or without PSS.
Electromechanical oscillations; synchronous generator; input shaping; ZV; ZVD; ZVDD
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano