Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

Capacity Optimization of Renewable Energy Sources and Battery Storage in an Autonomous Telecommunication Facility (CROSBI ID 205652)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Dragičević, Tomislav ; Pandžić, Hrvoje ; Škrlec, Davor ; Kuzle, Igor ; Guerrero, Josep M. ; Kirschen, Daniel S. Capacity Optimization of Renewable Energy Sources and Battery Storage in an Autonomous Telecommunication Facility // IEEE Transactions on Sustainable Energy, 5 (2014), 4; 1367-1378. doi: 10.1109/TSTE.2014.2316480

Podaci o odgovornosti

Dragičević, Tomislav ; Pandžić, Hrvoje ; Škrlec, Davor ; Kuzle, Igor ; Guerrero, Josep M. ; Kirschen, Daniel S.

engleski

Capacity Optimization of Renewable Energy Sources and Battery Storage in an Autonomous Telecommunication Facility

This paper describes a robust optimization approach to minimize the total cost of supplying a remote telecommunication station exclusively by renewable energy sources (RES). Due to the intermittent nature of RES, such as photovoltaic (PV) panels and small wind turbines, they are normally supported by a central energy storage system (ESS), consisting of a battery and a fuel cell. The optimization is carried out as a robust mixed- integer linear program (RMILP), and results in different optimal solutions, depending on budgets of uncertainty, each of which yields different RES and storage capacities. These solutions are then tested against a set of possible outcomes, thus simulating the future operation of the system. Since battery cycling is inevitable in this application, an algorithm that counts the number of cycles and associated depths of discharges (DoD) is applied to the optimization results. The annual capacity reduction that results from these cycles is calculated for two types of battery technologies, i.e., valve- regulated lead–acid (VRLA) and lithium–ion (Li– ion), and treated as an additional cost. Finally, all associated costs are added up and the ideal configuration is proposed.

autonomous power facility; batteries; energy storage system (ESS); renewable energy sources (RES); robust mixed-integer linear program (RMILP)

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

5 (4)

2014.

1367-1378

objavljeno

1949-3029

10.1109/TSTE.2014.2316480

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost