Unsymmetrical load of a three-phase synchronous generator (CROSBI ID 195588)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Maljković, Zlatko ; Žarko, Damir ; Stipetić, Stjepan Unsymmetrical load of a three-phase synchronous generator // Przegląd elektrotechniczny, 2013 (2013), 2b; 68-71

Podaci o odgovornosti

Maljković, Zlatko ; Žarko, Damir ; Stipetić, Stjepan

engleski

Unsymmetrical load of a three-phase synchronous generator

The selection of a three phase synchronous generator most suitable to be used as a power supply for testing of single-phase and threephase power transformers is described in the paper. The emphasis is on the analysis of the armature winding connection and sizing of the damper winding due to unsymmetrical load of a generator in the temperature rise test of single-phase transformers realized by the short-circuit method. The generator’s output voltage waveforms in the case of unskewed and skewed stator slots are analyzed. The results indicate that delta connected generator with skewed stator slots is the best solution.

synchronous generator ; unsymmetrical load ; damper bar ; transformer testing