Switching Transients in 400 kV Transmission Network due to Circuit Breaker Failure (CROSBI ID 598583)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Bojić, Srećko ; Uglešić, Ivo ; Filipović-Grčić, Božidar
engleski
Switching Transients in 400 kV Transmission Network due to Circuit Breaker Failure
The paper presents the case study of SF6 circuit breaker failure during switching-off an unloaded and relative long 400 kV transmission line. Both breaking chambers of the circuit breaker were destroyed. Due to the specific place and type of fault the relay protection system did not operate during circuit breaker failure and transients have been recorded only by a power quality monitoring system installed in the nearby line bay. Recorded events were used for circuit breaker post-mortem analysis. Simulations and fault analysis were carried out using EMTP-RV software.
400 kV circuit breaker failure; restrike; transient recovery voltage; switching