Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Impact of electromagnetic shields on local overheating in transformer tank (CROSBI ID 588311)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Sitar, Robert ; Janić, Žarko Impact of electromagnetic shields on local overheating in transformer tank // International Colloquium Transformer Research and Asset Management, Dubrovnik, 2012. 2012

Podaci o odgovornosti

Sitar, Robert ; Janić, Žarko

engleski

Impact of electromagnetic shields on local overheating in transformer tank

The paper describes different influences of magnetic and electromagnetic shielding on stray flux distribution in power transformers. The application of electromagnetic shields on the reduction of high temperature spots in transformer tank is studied in detail by using a 3D model for a coupled electromagnetic-thermal calculation. The analysis of transformer models with various shapes and dimensions of electromagnetic shields show which factors are the most important for reduction of temperature hot spots in the tank. Proposed shielding solution should reduce the total stray loss and maximum temperature value. It is shown that the reduction of these values is not always achieved by shielding most of the area endangered by the stray flux from the high current leads. The choice of the shield must take into account the surrounding component material properties and transformer lead arrangement.

coupled calculation; electromagnetic shielding; high current leads; stray flux; transformer

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

2012.

objavljeno

Podaci o matičnoj publikaciji

Podaci o skupu

International Colloquium Transformer Research and Asset Management, Dubrovnik, 2012

predavanje

16.05.2012-18.05.2012

Dubrovnik, Hrvatska

Povezanost rada

Elektrotehnika