Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

Measurement and calculation of harmonics in distribution power system with connected small co- generation facility Etan (CROSBI ID 550505)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Tomasović Teklić, Ana ; Lasić, Mate ; Filipović-Grčić, Božidar Measurement and calculation of harmonics in distribution power system with connected small co- generation facility Etan // International Conference on Renewable Energies and Power Quality (ICREPQ’ 09), Valencia (Spain) 15th to 17th April, 2009. / European Association for the evelopment of Renewable Energies (ur.). Valencia: European Association for the evelopment of Renewable Energies, 2009. str. 1-4

Podaci o odgovornosti

Tomasović Teklić, Ana ; Lasić, Mate ; Filipović-Grčić, Božidar

engleski

Measurement and calculation of harmonics in distribution power system with connected small co- generation facility Etan

Generation of electrical energy in large conventional plants (thermal, hydro, nuclear) in last ten years worldwide is being supplemented by small generation utilities. Etan is a gas refining facility. Power supply is provided by two turbo generators and each of them can independently cover the consumption of Etan. Etan usually works in insular operation, but it can also work parallel to the distribution system, especially in cases of maintenance of generator units. Etan is connected to the MV distribution power system (10 kV bus in substation 35/10 kV Ivanic Grad) through a 4, 5 km long cable. Load in Etan consist mostly of induction motors. Power electronic devices are used for control of motor loads. The working process of the refinery is always the same so the load is not varying with time. It is very important to know the influence of this kind of industrial consumers with distributed generation on power quality. Power quality measurements were performed at three measurement points with the power quality analyzer ION 7650 of company Power Measurement. The aim of this paper is to compare harmonic measurements and calculations at all three measuring points in different operating conditions depending on the production of generator in Etan.

Distributed generation; power quality; harmonic measurements; harmonic calculation.

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

1-4.

2009.

objavljeno

Podaci o matičnoj publikaciji

International Conference on Renewable Energies and Power Quality (ICREPQ’ 09), Valencia (Spain) 15th to 17th April, 2009.

European Association for the evelopment of Renewable Energies

Valencia: European Association for the evelopment of Renewable Energies

Podaci o skupu

International Conference on Renewable Energies and Power Quality (ICREPQ’ 09), Valencia (Spain) 15th to 17th April, 2009.

predavanje

15.04.2009-17.04.2009

Valencia, Španjolska

Povezanost rada

Elektrotehnika