Earthing System Evaluation and Influence on Protection Performance in Resonanltly Earthed MV Networks (CROSBI ID 547807)
Prilog sa skupa u zborniku | stručni rad | međunarodna recenzija
Podaci o odgovornosti
Hutter, Sandra
engleski
Earthing System Evaluation and Influence on Protection Performance in Resonanltly Earthed MV Networks
In Zagreb distribution area, Petersen coils are installed in five 110/10(20) kV substations. The advantages of resonantly earthed MV networks (continuous operation, arc self-extinction etc.) and some disadvantages (lower protection sensitivity) are well known. An overview of the procedure implemented before putting Peterson coils in operation is given, with emphasis on the earthing system evaluation, which has proved to be rather important. Protection testing should be performed for different types of faults. All data are given for two distribution areas in which Peterson coils have been recently installed.
earthing resistance; resonanltly earthed network; Petersen coil