Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

3D finite-element determination of stray losses in power transformer (CROSBI ID 138842)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Šušnjić, Livio ; Haznadar, Zijad ; Valković, Zvonimir 3D finite-element determination of stray losses in power transformer // Electric power systems research, 78 (2008), 10; 1814-1818

Podaci o odgovornosti

Šušnjić, Livio ; Haznadar, Zijad ; Valković, Zvonimir

engleski

3D finite-element determination of stray losses in power transformer

This paper presents a three dimensional finite-element (FE) analysis of eddy current losses generated in the tank walls and yoke clamps of a three-phase 40 MVA power transformer. The time harmonic FE model is used to compute the magnetic leakage field in the case of a short circuit condition of the power transformer. Three cases are analyzed to study the impact of modeling tank walls and yoke clamp plates in FE context in estimation of their losses. The load loss test was carried out on an experimental transformer to validate the simulation.

Stray losses; Finite-element analyses; Eddy currents; Power transformer

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

78 (10)

2008.

1814-1818

objavljeno

0378-7796

Povezanost rada

Elektrotehnika

Indeksiranost