Surge Protection of Low-Voltage Systems Connected to Overhead Line (CROSBI ID 523380)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Uglešić, Ivo ; Milardić, Viktor Surge Protection of Low-Voltage Systems Connected to Overhead Line // Proceedings of 28th Internationl Conference on Lightning Protection / Mazzetti, Carlo (ur.). Kanazawa: ICLP, 2006. str. 1086-1091-x

Podaci o odgovornosti

Uglešić, Ivo ; Milardić, Viktor

engleski

Surge Protection of Low-Voltage Systems Connected to Overhead Line

A procedure of choosing the appropriate surge protective device for low-voltage systems is presented. For typical surge protection application an appropriate EMTP model is devised. The energy overload is calculated for a surge protective device following a simulation of the lightning effect. In this way it is possible to determine a required class for a surge protective device in question. The procedure is tested on some typical overhead low-voltage network. According to calculation results and very good service experiences, Class II surge protective devices can be adequately used for service entrance of buildings.

overhead low-voltage network; surge protective device classes; probability of energy overloading; procedure; protected building

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

1086-1091-x.

2006.

objavljeno

Podaci o matičnoj publikaciji

Proceedings of 28th Internationl Conference on Lightning Protection

Mazzetti, Carlo

Kanazawa: ICLP

Podaci o skupu

28th Internationl Conference on Lightning Protection

predavanje

18.09.2006-22.09.2006

Kanazawa, Japan

Povezanost rada

Elektrotehnika