An improvement of electrical motor insulation condition testing (CROSBI ID 469888)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Ban, Drago ; Cettolo, Mirko ; Miletić, Boris
engleski
An improvement of electrical motor insulation condition testing
This paper presents one of the maintenance test methods and the results of its application in the determination of the insulation condition of high-voltage electric motors. Testing and data processing were carried out on site using a PC and adequate software. Automatization eases and speeds the testing and the interpretation of results. This method is a modification of the Höfler method. Highly stabilized dc voltage is applied to the motor windings in 5 steps, from 0.3 Un to 1.5 Un, in steps of 0.3 Un, while at the same time the leakage currents are being measured. In the case of "ideal insulation", leakage currents are proportional to the applied dc voltage, i.e. the insulation resistance is independent of the applied voltage. In reality, insulation resistance and leakage currents depend on the applied voltage. The ways the leakage current depends on voltage and its magnitude can be used to determine the insulation condition. The insulation condition is estimated based on the non-linearity coefficients value.
electrical motor; insulation; condition testing
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
56-62-x.
1998.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the 10th EDPE Conference
Podaci o skupu
10th EDPE Conference
predavanje
14.10.1998-16.10.1998
Dubrovnik, Hrvatska