Determination of Operating Limits of Underexcited Synchronous Generator by Measurements (CROSBI ID 520980)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Maljković, Zlatko ; Ilić, Ivan ; Gašparac, Ivan ; Pavlica, Milutin ; Višković, Alfredo ; Andročec, Ivan
engleski
Determination of Operating Limits of Underexcited Synchronous Generator by Measurements
In the underexcitation quadrant, standard power chart of synchronous generator has its limit defined by practical stability limit and by field current minimum. However, during the time, some generators have shown certain sensitivity during the permanent underexcited operation even in the stabile operating area due to local heating of magnetic conductive parts in the end region of the machine. Underexcited operation is usually required in case of raised network voltage while the active power demands are lowered. Precise knowledge of limits of underexcited operation ability enables precise planning of system reactive power trading. Some world experiences, axial magnetic field measurements, as well as local heating measurements in the end region of synchronous generator are presented. Based on mentioned measurements, it is possible to define real power chart which almost always deviates in capacitive operating area compared to manufacturer's diagram.
Synchronous generator – underexcitation - power chart - local heating
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
A1 204 ; 1-8-x.
2006.
objavljeno
Podaci o matičnoj publikaciji
Cigre Session 41
Pariz: CIGRÉ
Podaci o skupu
Cigre Session 41
predavanje
27.08.2006-01.09.2006
Pariz, Francuska