A Simple Measurement for Harmonic Source Localization (CROSBI ID 498697)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Vlahinić, Saša ; Vlahinić, Ivan ; Brnobić, Dalibor
engleski
A Simple Measurement for Harmonic Source Localization
A simple measurement is proposed for source identification and characterization. Power transformer is proposed as a point to perform the measurements in a cheap and practical way. Simulation has been undertaken to confirm validity of the proposed method. The procedure for the load characterization, outlined in this paper, has been tested in real power distribution system to establish the contribution of the certain industrial customer to the harmonic distortion. In contrary to previous assumption, it has been found out that the analyzed customer is not dominant source of distortion and is only partially responsible for the harmonic distortion at the PCC.
harmonic; measurements; source localization
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
991-994-x.
2004.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of MELECON 2004 The 12th Mediterranean Electrotechnical Conference
Matijašević, Maja ; Pejčinović, Branimir ; Tomšić, Željko ; Butković, Željko
Zagreb: Institute of Electrical and Electronics Engineers (IEEE)
Podaci o skupu
The 12th Mediterranean Electrotechnical Conference - MELECON 2004
predavanje
12.05.2004-15.05.2004
Dubrovnik, Hrvatska