A simple measurment for harmonic source localization (CROSBI ID 496684)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Vlahinić, Saša ; Vlahinić, Ivan ; Brnobić, Dalibor A simple measurment for harmonic source localization. 2004

Podaci o odgovornosti

Vlahinić, Saša ; Vlahinić, Ivan ; Brnobić, Dalibor

engleski

A simple measurment for harmonic source localization

Simple measurement is proposed for source identification and characterization. Power transformer is proposed as a point to perform the maesurement in a cheap and practical way. Simulation has been undertaken to confirm validity of the proposed method. The procedure for the load characterization, outlined in this paper, has been tested in real power distribution system to establish the contribution of the certain industrial customer to the harmonic distortion. In contrary to previous assumption, it has been found out that the analyzed customer is not dominant source of distortion and is only partially responsible for the harmonic distortion at the PCC.

Simple measurement; harmonic source localization