Current reduction factor of compensation conductors laid alongside three single-core cables in flat formation (CROSBI ID 491777)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Sarajčev, Ivan ; Majstrović, Matislav ; Medić, Ivan
engleski
Current reduction factor of compensation conductors laid alongside three single-core cables in flat formation
The three-phase cable line consists of three single-core cables, which can have conductive sheaths, grounded at either one end only, or at both ends. If they are grounded at both ends, currents flow through sheaths of single-core cables during both balanced and unbalanced loads and the line-to-ground short circuit in the grounded network. During the line-to-ground short circuit, currents flow through cable sheaths and through the ground. When cable sheaths are grounded at one end only, currents do not flow through the sheaths and the influence of the short circuit on neighboring electrical circuits is greatest. Compensation conductors are used to reduce this effect. Reduction effect of compensation conductors laid alongside three power single-core cables in flat formation is analyzed in this paper. Calculation methods of current reduction factor are also described.
reduction factor; current; single-core cable; sheath; compensation conductor
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
2003.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the 2003 IEEE International Symposium on Electromagnetic Compatibility (EMC)
Joffe, Elya B.
Istanbul: IEEE EMC Society
Podaci o skupu
The 2003 IEEE International Symposium on Electromagnetic Compatibility (EMC)
predavanje
11.05.2003-16.05.2003
Istanbul, Turska