Compatibility of Transformer Materials with Insulating Liquids (CROSBI ID 722975)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Atanasova-Höhlein, I. ; Haramija, Veronika ; Vrsaljko, Dijana Compatibility of Transformer Materials with Insulating Liquids // CIGRE Paris, Session 2022. Pariz: CIGRÉ, 2022. str. 1-8

Podaci o odgovornosti

Atanasova-Höhlein, I. ; Haramija, Veronika ; Vrsaljko, Dijana

engleski

Compatibility of Transformer Materials with Insulating Liquids

Compatibility studies of materials with insulating liquids is a compulsory step in the design of liquid filled electrical equipment, e.g. transformers, reactors, bushings and similar equipment [1]. The changes in the insulating liquid to the new stage, as well as its influence on the tested material shall be evaluated. There are only a few adequate international established standard procedures, describing the testing methodology to a certain extent [2, 3], however, without providing of limit values. An incompatible material may have a detrimental influence on the dielectric properties of a liquid, thus jeopardizing its service or producing fault gases interfering with the Gas-in-Oil (DGA) interpretation. Its mechanical and/or dielectric properties can be strongly reduced, thus leading to a much shorter life span than expected. Testing procedures and pass/fail criteria are urgently necessary for the evaluation of materials not only in mineral oil, but also in other insulating liquids on the market like synthetic and natural ester, synthetic liquids, silicones etc. Proposal for the testing ratios of materials with insulating liquids, as well as limit acceptable values for those materials are presented and discussed in the paper. This methodology can be extended on further construction materials. This experience is based on a long term experience of a big transformer manufacturer.

Compatibility, transformer materials, insulating liquids, mineral oil, synthetic ester, natural ester, silicone liquid, material properties, liquid properties

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

1-8.

2022.

objavljeno

Podaci o matičnoj publikaciji

CIGRE Paris, Session 2022

Pariz: CIGRÉ

Podaci o skupu

CIGRE Paris Session 2022

predavanje

28.08.2022-02.09.2022

Pariz, Francuska

Povezanost rada

Kemija, Kemijsko inženjerstvo