Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

On Site Measurement and Simulation of Transferred Lightning Overvoltages Through Power Transformers (chapter in book) (CROSBI ID 73695)

Prilog u knjizi | izvorni znanstveni rad | međunarodna recenzija

Jurišić, Bruno ; Župan, Tomislav ; Plišić, Goran ; Filipović-Grčić, Božidar ; Levačić, Goran ; Xemard, Alain On Site Measurement and Simulation of Transferred Lightning Overvoltages Through Power Transformers (chapter in book) // 5th International Colloquium on Transformer Research and Asset Management / Trkulja, Bojan ; Štih, Željko ; Janić, Žarko (ur.). Singapur: Springer, 2020. str. 145-162 doi: 10.1007/978-981-15-5600-5_13

Podaci o odgovornosti

Jurišić, Bruno ; Župan, Tomislav ; Plišić, Goran ; Filipović-Grčić, Božidar ; Levačić, Goran ; Xemard, Alain

engleski

On Site Measurement and Simulation of Transferred Lightning Overvoltages Through Power Transformers (chapter in book)

High voltage electrical devices such as power transformers are often stressed by the overvoltages that occur during switching operation and atmospheric discharges. Consequently, it is of particular interest to monitor these events in the power network. Nowadays, power transformers can be equipped with transient recorders that measure the voltages at the bushing measurement taps. It is possible to simulate events captured by these recorders, in EMTP. In this process, the crucial element that has to be modelled properly is the power transformer. In this paper, three wideband transformer models are presented: black-box, grey-box and white-box. These models are validated using the transmitted overvoltage measurements at high voltage laboratory. Then, the results of the simulation of the transient event recorded in 220/110 kV substation is presented and compared to the on site measurements results.

Transient recorder ; On site measurements ; Wideband transformer model ; Lightning ; EMTP

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

145-162.

objavljeno

10.1007/978-981-15-5600-5_13

Podaci o knjizi

5th International Colloquium on Transformer Research and Asset Management

Trkulja, Bojan ; Štih, Željko ; Janić, Žarko

Singapur: Springer

2020.

978-981-15-5599-2

1876-1100

1876-1119

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost