Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Analysis of Overvoltages on Power Transformer Recorded by Transient Overvoltage Monitoring System (chapter in book) (CROSBI ID 73694)

Prilog u knjizi | izvorni znanstveni rad | međunarodna recenzija

Filipović-Grčić, Božidar ; Jurišić, Bruno ; Keitoue, Samir ; Murat, Ivan ; Filipović-Grčić, Dalibor ; Župan , Alan Analysis of Overvoltages on Power Transformer Recorded by Transient Overvoltage Monitoring System (chapter in book) // 5th International Colloquium on Transformer Research and Asset Management / Trkulja, Bojan ; Štih, Željko ; Janić, Žarko (ur.). Singapur: Springer, 2020. str. 85-102 doi: 10.1007/978-981-15-5600-5

Podaci o odgovornosti

Filipović-Grčić, Božidar ; Jurišić, Bruno ; Keitoue, Samir ; Murat, Ivan ; Filipović-Grčić, Dalibor ; Župan , Alan

engleski

Analysis of Overvoltages on Power Transformer Recorded by Transient Overvoltage Monitoring System (chapter in book)

In this paper, an on-line transient overvoltage monitoring system (TOMS) for power transformers is used for measurement of overvoltages on the transformer bushing tap. The focus of the paper is on the analysis of transient overvoltages caused by lightning strikes recorded at the terminals of power transformer. Several recorded overvoltages are analyzed and their amplitudes and frequency spectrum are presented and compared with those referring to standard impulse voltages from IEC standard. Collected data include number, peak and duration of recorded transient overvoltages and can be used for the assessment of the transformer insulation condition and estimation of health index. Data recorded by TOMS are also of significant importance since the insulation system of power transformer and other equipment in the substation can be damaged by lightning or switching overvoltages.

Monitoring system ; Power transformer ; Lightning overvoltages ; Frequency spectrum ; Insulation

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

85-102.

objavljeno

10.1007/978-981-15-5600-5

Podaci o knjizi

5th International Colloquium on Transformer Research and Asset Management

Trkulja, Bojan ; Štih, Željko ; Janić, Žarko

Singapur: Springer

2020.

978-981-15-5599-2

1876-1100

1876-1119

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost