Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Analiza atmosferskih prenapona na energetskim transformatorima (CROSBI ID 451099)

Ocjenski rad | diplomski rad

Vojvodić, Matej Analiza atmosferskih prenapona na energetskim transformatorima / Filipović-Grčić, Božidar ; Jurišić, Bruno (mentor); Zagreb, Fakultet elektrotehnike i računarstva, . 2021

Podaci o odgovornosti

Vojvodić, Matej

Filipović-Grčić, Božidar ; Jurišić, Bruno

hrvatski

Analiza atmosferskih prenapona na energetskim transformatorima

Diplomski rad opisuje i analizira neke od ključnih utjecaja atmosferskih prenapona na tipične energetske transformatore kakvi se koriste u postrojenjima za prijenos i distribuciju električne energije. Za potrebe rada izrađen je detaljni model transformatorske stanice 220/110 kV kako bi se sam utjecaj prenapona mogao promatrati tokom pogona. Posebna je pažnja posvećena modeliranju transformatorske stanice i energetskog transformatora kao elementa od ključnog značaja. Promatrana su dva različita modela transformatora na kojima su izračunati preneseni atmosferski prenaponi u praznom hodu i u pogonu transformatora. Simulacije su se temeljile na stvarno izmjerenim prenaponima u postrojenju i time se otvorila mogućnost usporedbe dobivenih rezultata sa zabilježenim događajima u pogonu. Cilj rada bio je uvidjeti sličnosti i razlike u ponašanju visokofrekvencijskog i niskofrekvencijskog BCTRAN modela transformatora proširenog sa kapacitetima za različite valne oblike atmosferskih prenapona. The objective of this master thesis is to describe and show some of the key factors of influence of lightning overvoltages on typical power transformers which are used transmission and distribution substations. A detailed simulation model of the substation 220/110 kV has been developed for the purpose of the thesis, in order to analyze the influence of overvoltages on transformers in operation. A special attention has been paid to the modelling of the substation and power transformer as the most important element. Two different models of power transformers have been used for calculation of transmitted overvoltages in case of unloaded transformer and while in operation. Simulations have been based on the real measured overvoltages in the substation which opened up the possibility to compare the obtained results with the recorded overvoltages at power transformer terminals while in operation. The aim of this analysis is to identify differences and similarities between high- frequency and low-frequency BCTRAN (extended with capacitances) models of power transformers with respect to different lightning overvoltage waveforms.

energetski transformator ; modeliranje ; atmosferski prenaponi ; visokofrekvencijski model ; prijelazne pojave

nije evidentirano

engleski

Analysis of lightning overvoltages on power transformers

nije evidentirano

power transformers ; modelling ; lightning overvoltage ; high-frequency model ; transients

nije evidentirano

Podaci o izdanju

97

06.07.2021.

obranjeno

Podaci o ustanovi koja je dodijelila akademski stupanj

Fakultet elektrotehnike i računarstva

Zagreb

Povezanost rada

Elektrotehnika