Improved Model of Thermal Rotor Protection Including Negative Sequence Protection (CROSBI ID 307632)
Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Burgund, Davorin ; Nikolovski, Srete
engleski
Improved Model of Thermal Rotor Protection Including Negative Sequence Protection
The paper presents a new model of the thermal rotor protection 49R on synchronous generators with self-excitation with the influence of generator negative sequence protection 46I2. The purpose of the analysis is to solve the problem of simultaneous occurrence of rotor overload due to excitation current and rotor overload due to the inverse component of the stator current. The numerical protections are designed to operate independently of each other, and therefore the residual thermal capacity of the copper windings is not defined with higher precision. A mathematical model that integrates these two protections is given and described.
rotor thermal protection ; negative sequence protection ; synchronous generator ; excitation system ; air‐cooled generator ; rotor temperature
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano