A Comprehensive Assessment of Fundamental Overcurrent Relay Operation Optimization Function and Its Constraints (CROSBI ID 305619)

Prilog u časopisu | pregledni rad (znanstveni) | međunarodna recenzija

Rojnić, Michele ; Prenc, Rene ; Bulat, Hrvoje ; Franković, Dubravko A Comprehensive Assessment of Fundamental Overcurrent Relay Operation Optimization Function and Its Constraints // Energies (Basel), 15 (2022), 4; 1-20. doi: 10.3390/en15041271

Podaci o odgovornosti

Rojnić, Michele ; Prenc, Rene ; Bulat, Hrvoje ; Franković, Dubravko

engleski

A Comprehensive Assessment of Fundamental Overcurrent Relay Operation Optimization Function and Its Constraints

The optimization of overcurrent relays’ operation is a topic associated with protection coordination of distribution networks. Usually, this refers to medium-voltage networks, since they are protected by numerical relay devices, as opposed to low-voltage networks, where utility operators allocate fuses. Correct setting of relays and optimal coordination is becoming a serious challenge to Distribution Network Operators around the world, since their networks’ passive operation has been greatly altered in the past two decades. Distributed generation units, a growing liberalized electricity market and more stringent legislation for distribution network planning and operation by state regulatory bodies have all indirectly affected the evolving of protection philosophy for distribution networks. In this paper the traditional optimization problem of overcurrent relay operation will be addressed and critically examined from both a theoretical and practical point of view. Optimization function, constraints and relay parameters will all be observed and compared with solutions used in distribution networks, and their modifications and improvements will be proposed and elaborated in detail.

overcurrent relays ; protection optimization ; plug settings ; time multiplier settings ; coordination time interval

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

15 (4)

2022.

1-20

objavljeno

1996-1073

10.3390/en15041271

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost