Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Modular Hierarchical Model Predictive Control for Coordinated and Holistic Energy Management of Buildings (CROSBI ID 299809)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Vašak, Mario ; Banjac, Anita ; Hure, Nikola ; Novak, Hrvoje ; Marušić, Danko ; Lešić, Vinko Modular Hierarchical Model Predictive Control for Coordinated and Holistic Energy Management of Buildings // IEEE transactions on energy conversion, 36 (2021), 4; 2670-2682. doi: 10.1109/TEC.2021.3116153

Podaci o odgovornosti

Vašak, Mario ; Banjac, Anita ; Hure, Nikola ; Novak, Hrvoje ; Marušić, Danko ; Lešić, Vinko

engleski

Modular Hierarchical Model Predictive Control for Coordinated and Holistic Energy Management of Buildings

Modular building energy management strategy based on a three-level hierarchical model predictive control is proposed in the paper. Building zones, central medium conditioning and microgrid subsystems are controlled independently by individual linear and nonlinear model predictive controllers, and further integrated together as levels of hierarchical coordination control structure based on price-consumption information exchange. The three-level coordination provides a holistic energy management strategy and enables significant demand response ancillary services for buildings as prosumers, while retaining the independence of required expertise in very different building subsystems. The approach is applied for daily operation scheduling of a full- scale building consisting of 248 offices. Models of building subsystems are obtained by identification procedures on measurement data. Compared to rule-based control, detailed realistic simulations show that the overall building operation cost for typical days in summer is reduced by 9-12% for level-by-level energy-optimal and by 15-24% for price-optimal, coordinated operation. The application of predictive control in the proposed way also improves the indoor comfort substantially.

Building energy management system, Zone comfort control, Central medium conditioning, Microgrid energy management, Hierarchical coordination, Model predictive control, Energy efficiency, Price-optimal control

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

36 (4)

2021.

2670-2682

objavljeno

0885-8969

1558-0059

10.1109/TEC.2021.3116153

Trošak objave rada u otvorenom pristupu

Povezanost rada

Elektrotehnika, Informacijske i komunikacijske znanosti, Računarstvo, Temeljne tehničke znanosti

Poveznice
Indeksiranost