Distinction of asymmetric load from eccentricity or synchronous electric generator winding fault using search coil measurements (CROSBI ID 296942)
Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Petrinić, Miroslav ; Tvorić, Stjepan ; Plavec, Eduard ; Zrakić, Bono
engleski
Distinction of asymmetric load from eccentricity or synchronous electric generator winding fault using search coil measurements
Forces acting on the stator teeth of the 400 kVA, 4 pole synchronous generator were analyzed for asymmetric electric load conditions. Measurement of the flux density was performed with the measuring coils installed on the stator teeth and calculations were done by Finite Element Method. The measured data was processed to determine the radial forces of the stator teeth through Maxwell stress tensor integration algorithm. The processed data was used for detection of asymmetric load condition. The methodology for distinction of the asymmetric load from the eccentricity or winding fault is presented. The parameters of the measuring coil sensors and their adequate position can be determined with Finite Element calculation before performing sensor installation on the machine.
Coils, Electric machines, Electromagnetic forces, Finite element methods, Generators, Load modelling, Numerical analysis, Voltage measurement.
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o izdanju
57 (5)
2021.
4776-4785
objavljeno
0093-9994
1939-9367
10.1109/TIA.2021.3093503