Core-type transformer short-circuit voltage calculation using conformal mapping (CROSBI ID 283636)
Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Jurković, Mario ; Žarko, Damir
engleski
Core-type transformer short-circuit voltage calculation using conformal mapping
This study describes a method for calculation of transformer short-circuit voltage using conformal mappings, which map the transformer longitudinal and transverse cross-section geometry to a unit disk where an analytical solution for magnetic flux density is obtained and then transformed back to the original domain. The short-circuit voltage is calculated by the integration of the magnetic energy of the leakage field in the windings and the space around windings, excluding the core. This method takes into account windings of different height, the fringing effect at the ends of the windings and any relative position of windings located on the same or different limbs. Also, it is possible to calculate the short-circuit voltage for multiple windings.
Short-circuit voltage, conformal mapping, Schwarz-Christoffel transformation
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o izdanju
14 (12)
2020.
2422-2430
objavljeno
1751-8660
1751-8679
10.1049/iet-epa.2020.0351