Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Overload Mitigation SIPS Based on DC Model Optimization and PMU Technology (CROSBI ID 275406)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Zbunjak, Zoran ; Kuzle, Igor ; Mađar, Dino Overload Mitigation SIPS Based on DC Model Optimization and PMU Technology // Tehnički vjesnik : znanstveno-stručni časopis tehničkih fakulteta Sveučilišta u Osijeku, 27 (2020), 1; 213-220. doi: 10.17559/TV-20181109235036

Podaci o odgovornosti

Zbunjak, Zoran ; Kuzle, Igor ; Mađar, Dino

engleski

Overload Mitigation SIPS Based on DC Model Optimization and PMU Technology

System integrity protection schemes (SIPS) supported by phasor measurement unit (PMU) technology are based on the concept of collecting information from remote stations, sending the information to a central concentrator that executes a decision-making algorithm and initiates specialized actions to prevent the spread of system disturbance. This paper gives application of overload mitigation SIPS. Described protection scheme is based on a mixed integer linear programming (MILP) optimization of the DC power flow model whose objective is to maximize total load on the observed part of the network. Inaccuracy of the used DC model and the actual state is replaced by using the PMU technology. In this way, the influence of reactive power that is ignored in the DC model power flow model calculation is replaced in real- time with real synchronized measurements. Described SIPS is tested on IEEE 14 busbar test system. Conducted simulations indicate that developed optimization algorithm can mitigate potential element overloads with extremely high accuracy by using load shedding methods. Example on real part of Croatian power transmission network is given at the end of paper. This specific analysis demonstrates benefits of using SIPS based on synchro phasors in real world.

optimization ; overload mitigation ; phasor measurement unit ; system integrity protection scheme

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

27 (1)

2020.

213-220

objavljeno

1330-3651

1848-6339

10.17559/TV-20181109235036

Trošak objave rada u otvorenom pristupu

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost