​Influence of Different Turret-Tank Connection Types on Transformer Turret Eddy Currents (CROSBI ID 684552)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Župan, Tomislav ; Jurišić, Bruno ; Kelemen, Franjo ​Influence of Different Turret-Tank Connection Types on Transformer Turret Eddy Currents // ISH 2019: Proceedings of the 21st International Symposium on High Voltage Engineering / Németh, Bálint (ur.). Berlin: Springer, 2020. str. 75-84 doi: 10.1007/978-3-030-31676-1_8

Podaci o odgovornosti

Župan, Tomislav ; Jurišić, Bruno ; Kelemen, Franjo

engleski

​Influence of Different Turret-Tank Connection Types on Transformer Turret Eddy Currents

All metal parts of the transformer tank are usually electrically con-nected and grounded in order to prevent the possibly hazardous floating poten-tial from emerging. The magnetic field of transformer leads and bushings’ con-ductors induces eddy currents on nearby metal parts such as tank top and bush-ing turrets. Since the above-mentioned electrical connections can form the un-wanted conducting path loops, the type of these connections can help in restrict-ing the eddy currents and consequently the losses in metal parts and the heat generated in them. This is especially true for high-current power transformers such as generator step-up units. This research presents calculated and measured results of the influence of different bushing turret-tank connection types on the induced eddy current values. The simulation results were obtained using the fi-nite element method based software. Comparison against the measurements shows that these eddy currents can be adequately modelled and predicted using calculations which can prove useful in the design phase of the transformer manufacturing process. By carefully choosing the connection type and the loca-tion of the shorting element, the eddy current conducting path loops can be re-stricted and therefore the values of these currents can be limited as well. This can, in turn, lead to lower local losses and reduced heating of the metal parts, all of which can be easily shown using Rogowski coils for current measurements and thermal imaging systems for thermography measurements, respectively.

Bushing, Eddy Currents, Losses, Power Transformer, Turret

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

75-84.

2020.

objavljeno

10.1007/978-3-030-31676-1_8

Podaci o matičnoj publikaciji

ISH 2019: Proceedings of the 21st International Symposium on High Voltage Engineering

Németh, Bálint

Berlin: Springer

978-3-030-31676-1

1876-1100

1876-1119

Podaci o skupu

Nepoznat skup

predavanje

29.02.1904-29.02.2096

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost