Analysis of Overvoltages on Power Transformer Recorded by Transient Overvoltage Monitoring System (CROSBI ID 681726)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Filipović-Grčić, Božidar ; Jurišić, Bruno ; Keitoue, Samir ; Murat, Ivan ; Filipović-Grčić, Dalibor ; Župan, Alan
engleski
Analysis of Overvoltages on Power Transformer Recorded by Transient Overvoltage Monitoring System
In this paper, an on-line transient overvoltage monitoring system (TOMS) for power transformers is used for measurement of overvoltages on the transformer bushing tap. The focus of the paper is on the analysis of transient overvoltages caused by lightning strikes recorded at the terminals of power transformer. Several recorded overvoltages are analyzed and their amplitudes and frequency spectrum are presented and compared with those referring to standard impulse voltages from IEC standard. Collected data include number, peak and duration of recorded transient overvoltages and can be used for the assessment of the transformer insulation condition and estimation of health index. Data recorded by TOMS are also of significant importance since the insulation system of power transformer and other equipment in the substation can be damaged by lightning or switching overvoltages.
Monitoring system ; Power transformer ; Lightning overvoltages ; Frequency spectrum ; Insulation
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1-9.
2019.
objavljeno
Podaci o matičnoj publikaciji
5th International Colloquium "Transformer Research and Asset Management"
Opatija: CIGRÉ
Podaci o skupu
5th International Colloquium on Transformer Research and Asset Management
predavanje
09.10.2019-12.10.2019
Opatija, Hrvatska