Napredna pretraga

Pregled bibliografske jedinice broj: 1025143

An Improved Method for Performance Testing of Partial Discharge Calibrators


Filipović-Grčić, Dalibor; Filipović-Grčić, Božidar; Novko, Ivan
An Improved Method for Performance Testing of Partial Discharge Calibrators // Proceedings of the 21st International Symposium on High Voltage Engineering / Németh, Bálint (ur.).
Basel: Springer International Publishing, 2020. str. 1-12 doi:10.1007/978-3-030-31680-8_128


Naslov
An Improved Method for Performance Testing of Partial Discharge Calibrators

Autori
Filipović-Grčić, Dalibor ; Filipović-Grčić, Božidar ; Novko, Ivan

Vrsta, podvrsta i kategorija rada
Poglavlja u knjigama, znanstveni

Knjiga
Proceedings of the 21st International Symposium on High Voltage Engineering

Urednik/ci
Németh, Bálint

Izdavač
Springer International Publishing

Grad
Basel

Godina
2020

Raspon stranica
1-12

ISBN
978-3-030-31679-2

Ključne riječi
Partial discharges ; Calibrator ; Calibration methods ; Charge measurement

Sažetak
Partial discharges occur because of insulation defects, when the electric field amplitude locally exceeds the dielectric strength of the cavities inside the insulating material. The thermal, chemical and electrical phenomena associated with the partial discharges are dangerous for insulation systems of high voltage equipment, as they can accelerate the aging process. Therefore, partial discharge tests are nowadays prescribed as routine tests for most of the high voltage devices. The calibration of a partial discharge measuring system is carried out to determine its scale factor before every test. The calibration is performed with partial discharge calibrator. IEC 60270 describes methods used for the evaluation of the actual charge generated by the calibrator. However, some factors that may influence the performance test results regarding the influence of circuit components, partial discharge measuring system’s linearity, bandwidth and pulse train response on calibration are not specified. This paper presents an improved method for performance testing of partial discharge calibrators. A reference partial discharge calibrator was used, and the traceability of calibration was established. Various effects on calibration procedure were investigated such as the influence of circuit components, partial discharge measuring system’s linearity, bandwidth and pulse train response on calibration. Performed tests in this paper showed that these factors cannot be neglected and therefore an improved method for performance testing of partial discharge calibrators is proposed which considers mentioned factors and minimizes their influence on the calibration procedure.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Ustanove
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb

Časopis indeksira:


  • Scopus


Citati