Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity (CROSBI ID 269525)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Piliškić, Silvia ; Uglešić, Ivo ; Jurišić, Bruno Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity // International journal of electrical power & energy systems, 116 (2020), 1, 6. doi: 10.1016/j.ijepes.2019.105547

Podaci o odgovornosti

Piliškić, Silvia ; Uglešić, Ivo ; Jurišić, Bruno

engleski

Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity

he paper demonstrates the importance of taking the frequency-dependence of the tower grounding impedance into account when studying the lightning performance of an overhead line located in an area with high soil resistivity. Towers’ impulse grounding impedance measurements and their rational approximations are used to construct a wideband model of the towers’ grounding electrodes in an EMTP-type software program. In order to examine the impact of tower grounding impedances, simulations of lightning strokes to the overhead line tower were performed using an EMTP-type tool in the following three different cases: constant grounding impedance of the tower hit by a lightning stroke, frequency-dependent tower grounding impedance and frequency-dependent tower grounding impedance for the tower equipped with a Line Surge Arrester (LSA) installed at the lowest phase. The simulations have shown the influence of the frequency-dependence of the tower grounding impedance on the level of the build-up voltage across the tower’s insulator string and consequently on the flashover occurrence in the observed configuration with a high soil resistivity.

Frequency dependence ; Lightning ; Overvoltage performance ; Line surge arrester

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

116

2020.

1

6

objavljeno

0142-0615

1879-3517

10.1016/j.ijepes.2019.105547

Povezanost rada

Elektrotehnika

Poveznice