Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Line-interactive UPS as Shunt Active Power Filter (CROSBI ID 681465)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Perić, Ante ; Šunde, Viktor ; Ban, Željko Line-interactive UPS as Shunt Active Power Filter // 2019 International Conference of Electrical Drives and Power Electronics (EDPE) Proceedings / Dudrik, Jaroslav ; Fedák, Vilim ; Kyslan, Karol et al. (ur.). Košice, 2019. str. 98-105

Podaci o odgovornosti

Perić, Ante ; Šunde, Viktor ; Ban, Željko

engleski

Line-interactive UPS as Shunt Active Power Filter

This paper describes a newly proposed solution for using the line-interactive uninterruptible power supply (UPS) system as a shunt active power filter. An overview of active power filters topologies and control strategies for active power filters are presented. The proposed solution is compared to similar solutions. Supercapacitors are proposed as a replacement for capacitors, that are used in all similar solutions at DC side of bidirectional inverter/rectifier. Bidirectional half-bridge DC/DC converter with transformer is proposed for energy transfer between supercapacitors and batteries. Two operation modes of the proposed solution are given. First, while there is a mains supply and the device is working as a shunt active power filter. Second, when the mains supply fails and the device is working as a uninterruptible power supply. Simplified Widrow-Hoff algorithm based on Artificial Neural Network is used in first operation mode and sinusoidal PWM modulation is used in second operation mode as a control strategy for bidirectional inverter/converter. The simulation experiments are done with multiple nonlinear loads, i.e., inductive and capacitive loads, connected to the point of common coupling. Experimental results confirm the presumed functionality of the suggested line-interactive UPS system for both operation modes.

uninterruptible power supply, shunt active power filter, supercapacitor, bidirectional half-bridge DC/DC converter

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

98-105.

2019.

objavljeno

Podaci o matičnoj publikaciji

2019 International Conference of Electrical Drives and Power Electronics (EDPE) Proceedings

Dudrik, Jaroslav ; Fedák, Vilim ; Kyslan, Karol ; Matuško, Jadranko

Košice:

978-1-7281-0388-4

Podaci o skupu

International Conference of Electrical Drives and Power Electronics (EDPE)

poster

24.09.2019-26.09.2019

Vysoké Tatry, Slovačka

Povezanost rada

Elektrotehnika